Outdoor Lighting Calculator
Voltage Drop · Wire Sizing · Transformer Load · NEC Compliant
System Configuration
Most common for residential
Tru-Scapes transformer
Individual cable per zone
Fixture Runs (1)
0W
0.00V(0.0%)
12.00V
0.00A
12V
Good (< 7% drop)
Warning (7–10% drop)
Critical (> 10% drop)
Recommendations
Wire Resistance Reference
| AWG | Ω/1000ft | Max Amps | Max Run @ 10W | Recommended Use |
|---|---|---|---|---|
| #10 | 1.19 | 30A | 250 ft | Long runs, heavy loads, multi-zone |
| #12 | 1.89 | 20A | 150 ft | Standard residential, most common |
| #14 | 3 | 15A | 100 ft | Short runs, light decorative fixtures |
| #16 | 4.77 | 13A | 60 ft | Very short runs only |
| #18 | 7.56 | 10A | 35 ft | Extension only, not recommended |
Tru-Scapes Transformer Sizing Guide
| Model | Max Load (80%) | Typical Fixtures @5W | Application |
|---|---|---|---|
| 75W | 60W | Up to 12 fixtures | Small residential / accent |
| 100W | 80W | Up to 16 fixtures | Small residential / accent |
| 200W | 160W | Up to 32 fixtures | Medium residential |
| 300W | 240W | Up to 48 fixtures | Large residential |
| 400W | 320W | Up to 64 fixtures | Large residential / commercial |
Voltage Drop Formula
// Voltage Drop Calculation
I (amps) = Total Watts ÷ Input Voltage
R (ohms) = Wire Ω/ft × Wire Length × 2
V_drop = I × R
V_out = V_in - V_drop
Drop% = (V_drop ÷ V_in) × 100
// NEC/ANSI Landscape Lighting Standard
Max allowable drop = 10%
Recommended operating range: 10.8V – 12.0V
How Voltage Drop Works
Every foot of wire has resistance. When current flows through that resistance, it creates a voltage drop — meaning fixtures at the end of a long run receive less voltage than those near the transformer. Low voltage fixtures are sensitive: operating below 10.8V reduces brightness and shortens bulb life, while exceeding 12.5V can cause premature failure.
The 80% Transformer Rule
Never load a transformer above 80% of its rated wattage. For example, a Tru-Scapes 200W transformer should carry no more than 160W of fixtures. This prevents overheating, extends transformer life, and leaves headroom for future expansion.
Home-Run vs. Daisy-Chain Wiring
Home-run (hub) wiring runs an individual cable from the transformer to each fixture zone — this is the most reliable method and keeps voltage drop calculations straightforward. Daisy-chain (series) wiring connects fixtures end-to-end along a single cable; voltage drop compounds along the chain since earlier wire segments carry current for all downstream fixtures.
Using Transformer Taps
Most quality low-voltage transformers, including Tru-Scapes models, have multiple voltage taps: 12V, 13V, 14V, and sometimes 15V. By selecting a higher tap, you compensate for voltage drop on longer runs. For example, if calculations show 1.5V of drop on a 150ft run, using the 14V tap ensures fixtures see approximately 12.5V — ideal operating range.
Wire Gauge Selection
#12 AWG is the industry standard for most residential landscape lighting. Use #10 AWG for runs over 150 feet or heavy loads. #14 AWG is acceptable for very short decorative runs under 75 feet. Thicker wire (lower AWG number) means less resistance and less voltage drop.
Splitting Long Runs
If a single run exceeds 10% voltage drop and upgrading wire gauge isn't practical, split the fixtures between two separate runs from the transformer. This halves the current on each run, dramatically reducing voltage drop. The calculator's recommendations will suggest this when appropriate.